Semiannual Sprinkler Inspection

Jesse S.

Brian R.

Jesse S.
Fire Alarm Service Call

Ryan H.
Annual Backflow, Sprinkler, Standpipe, Fire Alarm, Sequence Testing, Fire Extinguisher and Semiannual Kitchen Hood Inspections

Brian R.

Brian R.

Ryan H.
Sprinkler Inspection Quarterly Sprinkler Inspection - (5) Drys and (5) Wets

Thomas M.
Deficiency Repairs Repaired and retested fire bypass backflow preventer

Doug D.

Marc P.

Marc P.
Quarterly Sprinkler; Semi-Annual Hood Inspections Deficiency for Silent Knight PF0631 FA-2 Event Center: Event center panel has serveral communication troubles on the FACP. Suggested for Dry SPK-8 / SW Closet Valve Room: Tower 2 dry system in closet by elevators should have a sprinkler sign in the door Deficiency for Silent Knight 5820 XL FA-7 Tower 2: Tower 2 FACP had several phone/communication troubles (4) Deficiency for Silent Knight IFP 1000 FA-8 Security: Casino FACP has several troubles

Marc P.
Deficiency Repairs Deficiency for Silent Knight PF0631 FA-2 Event Center: Event center panel and voice panel batteries due ( women’s downstairs restroom ) 4 x 12v 8ah Deficiency for Silent Knight 5700 FA-5 Golf Course: Golf course clubhouse panel batteries due 2 x 12v 8ah Deficiency for Dry SPIPE-2 / West Garage: 2nd level west side standpipe cap missing (red plastic) Deficiency for Silent Knight IFP-50 FA-4 Warehouse: Warehouse facp and aes batteries due 3 x 12v 8ah Deficiency for Silent Knight 5820 XL FA-6 Tower 1: Tower 1 kitchen elevator did not recall with alarm from lobby and machine room Main facp panel batteries due 2 x 12v 8ah Deficiency for Silent Knight IFP 1000 FA-8 Security: Main casino facp , vip module and radionics dialer batteries due Located in surveillance server room 3 x 12v 8ah 2 x 12v 18ah

Marc P.
Deficiency Repairs Silent Knight PF0631 FA-2 Event Center: Event center panel and voice panel batteries due for replacement. (women’s downstairs restroom) 4 x 12v 8ah Silent Knight 5700 FA-5 Golf Course: Golf course clubhouse panel batteries due for replacement. 2 x 12v 8ah Dry SPIPE-2 / West Garage: 2nd level west side standpipe cap missing (red plastic) Silent Knight IFP-50 FA-4 Warehouse: Warehouse FACP and AES batteries due for replacement. 3 x 12v 8ah Silent Knight 5820 XL FA-6 Tower 1: Tower 1 kitchen elevator did not recall with alarm from lobby and machine room - Recommend troubleshooting. Main FACP batteries due for replacement. 2 x 12v 8ah Silent Knight 5820 XL FA-7 Tower 2: Tower 2 NAC panel batteries due for replacement. (door next to smoking area exit) 4x12v8ah Fire alarm panel room has no signage on the door. Silent Knight IFP 1000 FA-8 Security: Main casino FACP, VIP module and radionics dialer batteries due for replacement. Located in surveillance server room. 3 x 1

Marc P.
Quarterly Sprinkler Inspection - Elevator testing not done during annual

Brian R.

Brian R.
Mounted horn strobes

Caleb K.

Brian R.
No fire alarm relays hooked up to that particular damper. The hvac is controlled from rooftop unit duct detectors and those are all clear and normal. Recommend hvac company to look at motor. It’s powered from 120v AC

Brian R.
Disabled trouble zone until remodel is completed

Brian R.
Replaced main facp batteries hotel tower 2. Reset duct detector in hotel tower 1